Two transformers, both 25 kVA, both oil-immersed, both from the same works. One is rated 11 kV and weighs 285 kg. The other is rated 33 kV and weighs 625 kg.
Same output, more than twice the metal. Buyers notice the weight first, because it decides whether a truck with a small crane can set the unit or whether the site needs a bigger one.
THREE RATINGS, TWO VOLTAGES
The pattern repeats across the small range. At 50 kVA, the 11 kV unit is 425 kg and the 33 kV unit is 690 kg. At 100 kVA, 600 kg against 925 kg.
The losses move the same way. No-load loss goes from 90 W to 140 W at 25 kVA, from 130 W to 160 W at 50 kVA, from 200 W to 230 W at 100 kVA. Load loss goes from 500 W to 950 W, 910 W to 1,200 W, and 1,580 W to 2,010 W.
Footprint grows too. The 25 kVA unit goes from 700 by 450 by 935 mm to 1,100 by 980 by 1,420 mm. That is not a unit you slide into the same bay.
WHY SMALL UNITS PAY THE MOST FOR VOLTAGE
Insulation does not shrink with the rating. A 33 kV winding needs a certain distance to earth, a certain creepage over the bushing, and a certain clearance between phases, whatever the kVA behind it.
On a 2,000 kVA unit those distances are absorbed by a large core and tank. On a 25 kVA unit they are the machine. The weight penalty falls as capacity rises: 119 percent at 25 kVA, 62 percent at 50 kVA, 54 percent at 100 kVA.
So the rule of thumb is simple. The smaller the transformer, the more of its bulk is voltage and the less is capacity. A small distribution transformer from China is usually easy to move at 11 kV and awkward at 33 kV, for the same plate.
WHAT THE LOSSES DO OVER A YEAR
No-load loss runs every hour. At 90 W, a 25 kVA unit spends 788 kWh a year doing nothing. At 140 W it spends 1,226 kWh. The 33 kV version draws 438 kWh more before a single load is switched on.
Load loss is the other half, and there the gap is wider in percentage terms: 500 W against 950 W at 25 kVA. On a feeder that carries load most of the day, that difference is not small.
None of this makes the 33 kV unit a bad machine. It makes it a different purchase.
WHEN 33 KV IS THE SIMPLER ANSWER
If the site already receives 33 kV, a 25 kVA transformer can sit straight on that feeder. That removes a whole stage: no 33 kV to 11 kV step-down, no second substation, no second set of protection.
That is why small 33 kV units turn up on long rural feeders, at the end of a line where a 25 kVA load sits far from the source. Mini-grids and remote microgrids make the same trade: one transformer at the voltage that arrives, rather than two at a voltage that does not.
The 340 kg and the larger footprint are what skipping that stage weighs. Sometimes that is the better trade.
WHEN 11 KV WINS
If the site is inside an industrial park with its own 11 kV distribution, a 33 kV unit buys nothing. You carry insulation, bushings and a heavier tank, then step the voltage down again twenty metres later.
This is where buyers get it wrong most often, and usually in the other direction: they assume a higher voltage rating means a better transformer. It does not. It means a transformer built for a different network.
Practical checks before ordering: what voltage actually arrives at the fence, what the foundation can carry, what the crane can lift, and whether the cubicle has room for a wider unit. Rural networks and village-scale supplies are where those four answers differ most from a city project.
WHAT ELSE CHANGES WITH THE VOLTAGE
Bushing height changes the tank lid. Higher voltage means taller bushings, which means a taller overall unit and more clearance above it. In a container or a small kiosk, that height is often the limiting dimension rather than the footprint.
Protection changes too. A 33 kV unit usually sits behind a different breaker and a different set of settings than an 11 kV unit of the same kVA. Small networks feel this first, because they have the least room for a protection study.
WHO SUPPLIES IT
XIAOPAI supplies small distribution transformers from 6 kV to 35 kV, oil-immersed and dry-type, built in Wenzhou: oil-immersed units, dry-type units, and the switchgear that protects them.
The useful question for a small distribution transformer from China is not which voltage is better. It is which voltage arrives at the site, and how much metal you are willing to move to meet it.