A dry type transformer steps 10 or 11 kV down to 0.4 kV with no oil to sample or replace. A dry type transformer manufacturer china prints two loss figures on its data sheet, and they behave in opposite ways: one is fixed by the core, the other follows the load.
The cast-resin SCB10 range makes the split easy to see. One unit at 1,000 kVA, the SCB10-1000/11-0.4, carries 1,770 W of no-load loss and 8,130 W of load loss. Both become heat inside the enclosure, and both leave through it.
TWO COLUMNS, TWO DIFFERENT JOBS
No-load loss is measured with the secondary open. It comes from the core, it appears the moment the unit is energised, and it stays the same whether the plant runs at full rate or stands empty.
Load loss is measured with the secondary shorted and rated current in the windings. It rises with the square of the current, so at half load it is a quarter of the printed figure.
The open-circuit test shows what the iron does at rated voltage, and the short-circuit test shows what the copper does at rated current. Neither one tells you what the unit will do at your load.
Reading the two as one number hides all of this. Efficiency work starts with the definitions, and here the definitions are an open circuit and a short circuit.
THE COLUMN THAT RUNS ALL YEAR
A year holds 8,760 hours, and no-load loss is present for every one of them. At 1,770 W that comes to about 15,500 kWh before a single product leaves the line.
Load loss appears only when the load does. At 60 per cent load for 6,000 hours, 8,130 W works out to roughly 17,600 kWh, and the two columns together reach about 33,000 kWh.
This is why a unit with a lower load-loss figure can still consume more across a year. The fixed column keeps running through weekends, holidays and the hours when the line is down for service.
A meter on the incoming feeder records all of it. Metering that logs the hours lets the plant check the data sheet against its own readings.
THE SHARE MOVES WITH SIZE
On the 160 kVA unit the sheet prints 540 W and 2,130 W, so no-load is a fifth of the total. On the 1,000 kVA unit it is a little under a fifth.
Small units carry more core for their rating, which is why the fixed column weighs more of the whole. Large units tilt toward the winding column, and that column only appears when demand does.
A single-shift plant has a different balance again. Its load column stays small because the current is small for most of the day, and the fixed column becomes the larger half without anyone noticing.
The demand pattern decides which tilt matters. Load that swings through the day spends fewer hours in the load column than a plant running flat out.
A HIGHER VOLTAGE CLASS PRINTS MORE
At 750 kVA the sheet holds two builds, one at 12.45 kV and one at 34.5 kV. No-load loss moves from 1,377 W to 2,200 W for the same capacity, because the higher class needs more insulation distance inside the same window.
Insulation distance is set when the winding is wound, and it shows up later in the core diameter, the enclosure size and the weight on the drawing. It cannot be trimmed at the end of the build.
Nothing on the nameplate shows it. A dry type transformer manufacturer china builds to the voltage the buyer declares, and the fixed column changes with that declaration.
It is also why two quotes at the same kVA and different system voltages cannot be compared line by line. Efficiency rules in some markets now count the fixed column, which makes the gap visible.
THE TEST REPORT IS WHERE THE NUMBER COMES FROM
No-load loss and load loss are routine tests. They are measured on every unit rather than sampled from a family, and the report that ships with the transformer carries both figures next to its serial number.
The same report carries winding resistance, turns ratio and impedance, so the loss figures can be read against the design rather than taken on trust.
Ask for that report before comparing anything. A brochure figure is a design target, and a routine test figure is what the tank actually does.
HOW TO PUT TWO OFFERS ON ONE PAGE
A dry type transformer manufacturer china can send two units with the same kVA and different loss figures, so the comparison has to start from the buyer's hours. Apply one load rate and one annual running time to both sheets.
A plant on three shifts weights the fixed column heavily. A single-shift plant weights it less, and its load column never reaches the printed figure.
When the two totals land close, the decision moves to floor space and the maintenance model, and the loss table stops being the tie-breaker.
One agreed definition at the start of the comparison saves an argument at the end.