XIAOPAI Factory Price VSG-12 Series High Voltage Vacuum Circuit Breaker
Breaking | / | Phase | Three |
Rated | 50 | Model | VSG-12 |
Place | Zhejiang, | Brand | XIAOPAI |
Product | VSG-12 | Application | Operating |
Machanical | 10000 | Package | Standard |
Port | Shanghai | Poles | 3 |
Rated | 12 V | Rated | 50 Hz |
Type | Vacuum |
Product performance description
VSG-12 Vacuum Circuit BreakerVSG-12 model indoor Ac HV vacuum circuit breaker is a type of holistic
sealed HV switchgear with small volume and compact structure. It applies to power system of rated
voltage 12 kV/24 KV, three-phase AC 50/60 Hz, and used to control and protect electric apparatus and
circuit with frequent operation.
Manufacturing Technique


Details Images
Ambient condition:
1. Altitude:≤1000 m
2. Ambient temperature:-15°C~+40°C
3. Relative humidity: daiy average ≤95%, monhly average ≤90%
4. Earthquake intensity:≤ 8 degree
5.Applicable occasions should free from inflammables, explosives, corrosives and severe vibration.
Technical parameter
Technical specification
Item | Unit | Date | |
Rated voltage | kV | 12 | |
Rated short-time PF withstand voltage(1 min) | 42 | ||
Rated lighting impulse withstand voltage(peak) | 75 | ||
Rated frequency | Hz | 50 | |
Rated current | A | 630 A | 630 A |
Rated short-circuit breakingcurrent | kA | 25 | 31.5 |
Rated short-time withst andcurrent | 25 | 31.5 | |
Rated short-circuit durationtime | S | 4 | |
Rated peak withstand current | kA | 63 | 80 |
Rated short circuit making current | 63 | 80 | |
Secondary circuit PF withstand voltage(1 min) | V | 2000 | |
Rated breaking current of back to back capacitor bank | A | 630/400 | |
Opening time | mss | 20~50 | |
Closing time | 35~70 | ||
Mechanicallife | Times | 10000 | |
Electricity | E2 Class | ||
Rated voltage of closingoperation | V | AC 110 AC 220 DC 110 DC 220 | |
Rated voltage of opening operation | |||
Rated voltage of energy storage motor | |||
Rated power of energy storage motor | W | 90 | |
Energy storage time | S | ≤15 | |
Contacts space | mm | 11±1 | |
Over travel | 3±1 | ||
Three phase open-closeout sync | ms | ≤2 | |
Rated operation sequence | O-0.3 s-CO-180 s-CO |
CompanyIntroduction



1. Which series should I choose for my application?
ZN85 for general indoor medium-voltage duty, VSG-12 for indoor switchgear with withdrawable configuration, VF2-12 where a permanent-magnet actuator is preferred for lower maintenance, and ZW32 for pole-mounted or outdoor installations (including the 24 kV outdoor version). The deciding factor is the installation type, not the voltage alone.
2. What is the difference between fixed and withdrawable types?
Withdrawable breakers can be racked out for maintenance without opening the cable compartment, which shortens downtime. Fixed types are simpler and cheaper but require the panel to be isolated for breaker maintenance. The choice drives total cost of ownership more than purchase price.
3. Which ratings are available?
The range covers 12 kV, 24 kV and 40.5 kV classes with several current and short-circuit combinations per class. Because a "25 kA at 12 kV" rating is not the same statement as "25 kA at 24 kV", the exact rating must be fixed per voltage class in the technical agreement.
4. What operating mechanism do you offer?
Spring-charged stored-energy mechanisms as standard, with permanent-magnet actuators on the VF2-12 series. Both are available with manual charging and with motor charging for remote operation.
5. Does the breaker include interlocks?
Interlocks are a function of the panel, not of the breaker alone. When supplied as part of a switchgear assembly, the five safety interlocks are included and tested; when supplied as a loose breaker, the interlocking must be designed into the panel.
6. Which standard governs testing?
IEC 62271-100 for circuit breakers, with IEC 62271-1 for general requirements. Routine tests are performed on every unit; type-test reports are provided for the design family.
7. How is the vacuum interrupter life declared?
Electrical life and mechanical life are declared separately and are not interchangeable: mechanical life counts mechanism operations, while short-circuit interruptions are governed by the rated short-circuit breaking capacity. Both values are stated in the technical data sheet.
8. What about the load-switch fuse combination (FZRN)?
The FZRN1225-12D combines a vacuum load-break switch with high-voltage fuses for transformer protection, typically on the incoming circuit of a compact substation. It is a different device from a circuit breaker and is selected where fault levels allow fuse protection.