VSG-12 Series High Voltage Vacuum Circuit Breaker

+8613806536768
Contact Now
Detail




XIAOPAI Factory Price VSG-12 Series High Voltage Vacuum Circuit Breaker






Breaking
Capacity

/

Phase

Three
Phase

Rated
Frequency

50
Hz

Model
Number

VSG-12

Place
of
Origin

Zhejiang,
China

Brand
Name

XIAOPAI

Product
Name

VSG-12
Vacuum
Circuit
Breaker

Application

Operating
mechanism
and
VCB

Machanical
Life

10000
times

Package

Standard
Case

Port

Shanghai
or
Ningbo

Poles
Number

3

Rated
Voltage

12 V

Rated
Frequency

50 Hz

Type

Vacuum
Circuit
Breaker



Product performance description

VSG-12 Vacuum Circuit BreakerVSG-12 model indoor Ac HV vacuum circuit breaker is a type of holistic

sealed HV switchgear with small volume and compact structure. It applies to power system of rated

voltage 12 kV/24 KV, three-phase AC 50/60 Hz, and used to control and protect electric apparatus and

circuit with frequent operation.

Manufacturing Technique








Details Images

Ambient condition:

1. Altitude:≤1000 m

2. Ambient temperature:-15°C~+40°C

3. Relative humidity: daiy average ≤95%, monhly average ≤90%
4. Earthquake intensity:≤ 8 degree
5.Applicable occasions should free from inflammables, explosives, corrosives and severe vibration.

Technical parameter

Technical specification

Item

Unit

Date


Rated voltage

kV

12


Rated short-time PF withstand voltage(1 min)


42


Rated lighting impulse withstand voltage(peak)


75


Rated frequency

Hz

50


Rated current

A

630 A
1250

630 A
1250

Rated short-circuit breakingcurrent

kA

25

31.5

Rated short-time withst andcurrent


25

31.5

Rated short-circuit durationtime

S

4


Rated peak withstand current

kA

63

80

Rated short circuit making current


63

80

Secondary circuit PF withstand voltage(1 min)

V

2000


Rated breaking current of back to back capacitor bank

A

630/400


Opening time

mss

20~50


Closing time


35~70


Mechanicallife

Times

10000


Electricity
life


E2 Class


Rated voltage of closingoperation

V

AC 110 AC 220 DC 110 DC 220


Rated voltage of opening operation




Rated voltage of energy storage motor




Rated power of energy storage motor

W

90


Energy storage time

S

≤15


Contacts space

mm

11±1


Over travel


3±1


Three phase open-closeout sync

ms

≤2


Rated operation sequence


O-0.3 s-CO-180 s-CO


CompanyIntroduction














Frequently asked questions

1. Which series should I choose for my application?
ZN85 for general indoor medium-voltage duty, VSG-12 for indoor switchgear with withdrawable configuration, VF2-12 where a permanent-magnet actuator is preferred for lower maintenance, and ZW32 for pole-mounted or outdoor installations (including the 24 kV outdoor version). The deciding factor is the installation type, not the voltage alone.

2. What is the difference between fixed and withdrawable types?
Withdrawable breakers can be racked out for maintenance without opening the cable compartment, which shortens downtime. Fixed types are simpler and cheaper but require the panel to be isolated for breaker maintenance. The choice drives total cost of ownership more than purchase price.

3. Which ratings are available?
The range covers 12 kV, 24 kV and 40.5 kV classes with several current and short-circuit combinations per class. Because a "25 kA at 12 kV" rating is not the same statement as "25 kA at 24 kV", the exact rating must be fixed per voltage class in the technical agreement.

4. What operating mechanism do you offer?
Spring-charged stored-energy mechanisms as standard, with permanent-magnet actuators on the VF2-12 series. Both are available with manual charging and with motor charging for remote operation.

5. Does the breaker include interlocks?
Interlocks are a function of the panel, not of the breaker alone. When supplied as part of a switchgear assembly, the five safety interlocks are included and tested; when supplied as a loose breaker, the interlocking must be designed into the panel.

6. Which standard governs testing?
IEC 62271-100 for circuit breakers, with IEC 62271-1 for general requirements. Routine tests are performed on every unit; type-test reports are provided for the design family.

7. How is the vacuum interrupter life declared?
Electrical life and mechanical life are declared separately and are not interchangeable: mechanical life counts mechanism operations, while short-circuit interruptions are governed by the rated short-circuit breaking capacity. Both values are stated in the technical data sheet.

8. What about the load-switch fuse combination (FZRN)?
The FZRN1225-12D combines a vacuum load-break switch with high-voltage fuses for transformer protection, typically on the incoming circuit of a compact substation. It is a different device from a circuit breaker and is selected where fault levels allow fuse protection.

contact us