3. Exterior Layout
3.1 Dimensions
Note: for the corresponding power rating, refer to Section 9 “Technical Specifications” for the other parameters.

432*445*222 (5U)



3.2 Terminal Layout
3.2.1 Wiring Diagram, 1–3 kVA, Single-Phase Input / Single-Phase Output

3.2.2 Wiring Diagram, 5–6 kVA, Single-Phase Input / Single-Phase Output

The terminal layout is the same as above (see 3.2.1).
3.2.3 Wiring Diagram, 5–6 kVA, Three-Phase Input / Single-Phase Output

3.2.4 Wiring Diagram, 8–10 kVA, Single-Phase Input / Single-Phase Output


3.2.5 Wiring Diagram, 8–10 kVA, Three-Phase Input / Single-Phase Output


3.2.6 Wiring Diagram, 15 kVA, Single-Phase Input / Single-Phase Output

3.2.7 Wiring Diagram, 15 kVA, Three-Phase Input / Single-Phase Output


3.2.8 Wiring Diagram, 20–30 kVA, Three-Phase Input / Single-Phase Output


4. Operating Principle
4.1 UPS System Block Diagram

Note: the charger is an optional accessory.
4.2 Normal Operation
In normal operation the mains is filtered to remove high-frequency harmonics, rectified into direct current, converted by the inverter into a clean sine wave, and then fed to the load through the static switch and filter. (With the optional charger, the DC link also charges the battery bank and keeps it at full capacity.)

4.3 Mains Failure

When the mains fails, the DC input (battery) supplies the inverter directly. The inverter converts it into a clean sine wave, which reaches the load through the static switch and filter, so the load keeps receiving uninterrupted power.
4.4 Bypass Supply

The UPS transfers to bypass supply in the following six situations:
1. Inverter not started
2. Overload
3. Inverter fault
4. During start-up: within 20 seconds of pressing the ON button, while the UPS is soft-starting
5. During shutdown: after the OFF button is pressed (inverter off)
6. UPS overtemperature protection
5. Operating Modes
5.1 Single Unit Operation

(1) Mains mode: with the mains healthy, power passes through the input isolation transformer, rectifier, inverter, output isolation transformer and inverter static switch to the load, converting the mains into a 220 V / 50 Hz sine wave.
(2) Mains failure mode: when the mains fails, the DC system supplies the inverter, which feeds the load with a sine wave.
(3) Bypass mode: when the unit is not started, is overloaded, or has an inverter fault, the mains feeds the load through the bypass static switch.
5.2 Series Hot Standby
Connecting the output of the “slave” unit to the bypass input of the “master” unit gives series hot standby. If the master fails and transfers to bypass, the slave connected to the master’s bypass input feeds the load through its own inverter, keeping the supply reliable and stable. Only when master and slave both fail does the load fall back to unprotected bypass (mains) supply.

5.3 Parallel Operation (Optional)
Note: all UPS units in a parallel system must share the same bypass input, and the parallel communication cables must be connected correctly.
(1) When every unit in the parallel system is healthy, the units share the load equally.

(2) If any unit fails, it leaves the parallel system automatically and the remaining units feed the load. Once repaired, the unit can rejoin the system directly; the transfer is break-free (no transfer time) and does not affect the load.

(3) If all units fail or are not started, the load is fed from bypass.

6. Installation
6.1 Input and Output Current
Power kVA | Main input single-phase | Main input three-phase | Bypass input | UPS output | DC bus | DC bus |
220VDC | 110VDC | |||||
A | A | A | A | A | A | |
1 | 6.5 | — | 4.5 | 4.5 | 4.5 | 8.9 |
2 | 13.0 | — | 9.1 | 9.1 | 8.9 | 17.8 |
3 | 19.5 | — | 13.6 | 13.6 | 13.4 | 26.8 |
4 | 25.3 | 6.6 | 18.2 | 18.2 | 17.8 | 35.7 |
5 | 31.7 | 8.2 | 22.7 | 22.7 | 22.3 | 44.6 |
6 | 38.0 | 9.9 | 27.3 | 27.3 | 26.8 | 53.5 |
7.5 | 45.8 | 11.9 | 34.1 | 34.1 | 32.7 | 65.4 |
8 | 48.9 | 12.7 | 36.4 | 36.4 | 34.9 | 69.7 |
10 | 61.1 | 15.8 | 45.5 | 45.5 | 43.6 | 87.1 |
15 | 91.7 | 23.5 | 68.2 | 68.2 | 64.6 | 129.2 |
20 | — | 30.6 | 90.9 | 90.9 | 86.1 | — |
30 | — | 45.9 | 136.4 | 136.4 | 129.2 | — |
Note: the currents above apply at rated voltage and rated load. Select cables and breakers according to this table and to the actual on-site wiring length.
Caution: use a Type D breaker for the main input.
6.2 Inspection
Check the unit and its accessories on receipt (see the packing list). Report any damage or shortage to the carrier and the dealer immediately, and keep the packaging for future service.
6.3 Placement
Install the unit on a level floor with good ventilation and little dust. Do not operate it when temperature or humidity is outside the specified range.
Keep it away from open flame and direct sunlight, and protect it from rain. Do not install it where corrosive gases are present.
Operating ambient temperature: 0 °C to 40 °C
6.4 Installing Accessories
To use the DB9 serial port, plug the supplied serial cable into the DB9 connector and tighten the screws. For RS485, twisted-pair cable is recommended.
6.5 Installing the Battery Bank (DC Panel)
Connect the positive and negative poles of the battery bank (DC panel) to the corresponding terminals on the rear control board, and make sure the polarity is correct. If the polarity is reversed, the internal reverse-polarity protection operates and the unit will not start, which prevents damage to the equipment.
6.6 Connecting the AC Bypass Source
The UPS must have an AC bypass source so that it can transfer to bypass operation and keep feeding the load if a fault occurs. Connect the live, neutral and earth conductors of the bypass source to the corresponding terminals on the rear control board. For safety, the AC bypass source must be protected by a branch breaker.
6.7 Connecting the Load
Wire the output in accordance with the relevant electrical codes. Avoid overload and short-circuit operation, and provide a good earthing system; the earth conductor is used only as a reference point for this unit. Poor earthing causes interference and data-processing errors and affects both the UPS and the system, so have it corrected by a qualified technician promptly.