The Same 1,000 kVA, and Two Different Transformers

2026-10-26 09:30 XIAOPAI
XIAOPAI · Wenzhou Xiaopai Electric Power Technology Co., Ltd. · Zhejiang, China
Put two offers for a 1,000 kVA, 10 kV, Dyn11 transformer side by side and the first page is identical. Capacity, voltage ratio, vector group, frequency. All four match, because all four describe the connection rather than the machine. The rest of the answer sits in two columns further along the sheet, and those columns are often missing. That is not a trick. The enquiry asked for a capacity, so the offer gives a capacity. If nobody asks for no-load loss, nobody writes it down, and the buyer ends up comparing two transformers by the only number both of them printed.

WHAT THE TWO COLUMNS MEASURE

No-load loss is what the core consumes to stay magnetised. It is drawn from the moment the unit is energised to the moment it is switched off, and the load has nothing to do with it. Load loss is the copper. It rises with the square of the current, so the figure in a table applies only at rated current. At 40 percent load it is around 0.16 of that figure. The split between iron loss and copper loss is old textbook material, and the heat they produce is what the cooling system has to carry away. What matters at the desk is simpler: the two quantities come from two different tests. The open-circuit test gives no-load loss and no-load current, the short-circuit test gives impedance and load loss, and the sequence of transformer testing techniques behind both is routine work. A supplier who sends one column without the other has sent half a data sheet, and the no-load half is usually the one that goes missing.

S11-M AND S13-M AT THE SAME RATING

Both tables below come from the XIAOPAI catalogue for the oil-immersed transformer range: fully sealed, 50 Hz, Dyn11, with a tapping range of plus or minus 5 percent in steps of 2.5 percent. Same low-voltage side, same dimensions on the drawing.
Rating (kVA)S11-M no-load (W)S13-M no-load (W)Load loss at 75 C (W), both
6308105706,200
8009807007,500
10001,15083010,300
12501,36097012,000
16001,6401,17014,500
20002,0501,44017,500
The load-loss column is identical at every rating. The gap opens in the core: 240 W at 630 kVA, 320 W at 1,000 kVA, 610 W at 2,000 kVA. Whatever the higher grade buys, it buys it in iron. The copper is the same copper. The number in the model name is the performance level, so S11-M and S13-M are two grades of the same 10 kV sealed design rather than two product families. That is why the weight, the footprint and the connection stay put while one column moves. These levels are written against published loss standards, which is what makes a table checkable instead of merely believable. One caution when comparing sheets from different suppliers: load loss has to be stated at the same reference temperature, 75 C in these tables. A figure given at 85 C will read lower than a 75 C figure on the same machine, and the difference comes from the reference, not the transformer.

THE COLUMN THAT RUNS ALL YEAR

Take that 320 W at 1,000 kVA and multiply by the hours in a year. 2,803 kWh. Three units on one site carry roughly 8,400 kWh of the same difference, with the load profile untouched. This holds while the transformer is energised, which for a distribution unit is most of its life. A plant running one shift and a plant running three pay the same no-load figure. Load loss behaves better: at 40 percent load it drops to about a sixth of the rated value.

WHY THE GRADE IS A SITE DECISION

A better core uses more iron and returns the difference through the no-load column, which is why the choice belongs with the load profile rather than with a preference for newer numbers. Most of the engineering that decides this happens before the core is wound, and the levers are well documented in this outline of loss reduction at the design stage. Buyers who run the arithmetic before the enquiry tend to ask for two or three ratings in the same message, with the losses attached, and pick from that short list. There is a practical write-up on taking losses into account when buying that covers the same ground from the purchasing side. One thing the table cannot tell you: what the load actually looks like. Drives, rectifiers and LED lighting draw non-sinusoidal current, and harmonics add losses that no 50 Hz table accounts for. If the plant is full of variable-speed drives, the rated figures are a floor, not a forecast.

WHAT TO PUT IN THE SCHEDULE

Six lines, half a page, and all six appear in the XIAOPAI tables for every rating: - no-load loss in W, at the rating offered - load loss in W at 75 C, at the rating offered - no-load current, as a percentage of rated current - short-circuit impedance, as a percentage - oil mass and total mass, in kg - the routine test report for the serial number being shipped The last one cannot be copied from a catalogue, and it is the one that closes the loop on the other five. A routine report normally covers winding resistance, ratio, impedance and load loss, no-load loss and current, plus the applied and induced voltage checks, and the dielectric tests that go with them. If the report arrives with only a ratio check, the loss columns in the offer were never verified on that unit.

THE TANK IS NOT JUST A BOX

Losses are the part of the specification that runs, but the fittings decide what you can see and what protects the unit. A sealed distribution transformer carries less of this furniture than a transformer with a conservator, and the difference shows up in maintenance rather than in the table. There is a useful inventory of the common accessories on an oil-filled transformer, from the breather and the oil level gauge to the pressure relief device. On units with a conservator, the Buchholz relay sits in the pipe between the tank and the conservator and reacts to gas or oil surge. It is a mechanical device with a float and a flap, and it is the reason a slow internal fault gets noticed before it becomes a fire. A sudden pressure relay covers the faster case, where the pressure rises before any gas has had time to collect. None of that appears in a loss table, and none of it is optional on the units that carry it.

WHAT XIAOPAI SUPPLIES

Wenzhou Xiaopai Electric Power Technology designs and manufactures oil-immersed transformers in 6-10 kV and 35 kV classes: the S9-M, S10-M, S11-M, S13-M, S20-M and S22-M ranges. The distribution tables run from 30 to 2,500 kVA, and the 35 kV power transformer range is published to 31,500 kVA.

The dry-type range is tabulated the same way, so the two technologies can sit on one comparison sheet. Every rating in those tables carries its no-load loss, load loss at 75 C, no-load current, impedance and mass, so the comparison above can be made before the order rather than after commissioning. XIAOPAI publishes the tables for the same reason a buyer should ask for them: a capacity is a request, and a loss column is an answer. One more thing, and it is the easiest question in the whole process. Ask which grade is on the table, S11-M or S13-M, before the technical comparison starts. The two are the same size and the same connection, and they differ in a column that runs for the life of the installation. Asking later usually means asking after the drawings are approved.

ONE LINE FOR THE RECORD
A capacity tells you what fits. The loss columns tell you what you bought, and they are the first thing to ask a supplier for.